Kavaken flagged the transformer winding temperatures of one wind turbine: all three phases were 30.0% above the expected value and 29.5% above comparable turbines at the same wind farm. The risk was rated low, and the drift had built up over several weeks. Ambient temperature had fallen 18.3% over the same period, so the windings should have been cooling. Kavaken pointed to the transformer cooling fan or its ventilation path as the most likely cause. Nine days after the flag, at the annual maintenance, the site team found the transformer fan faulty and replaced the fan contactor.
The weather cooled, the windings did not
Over the 14 days before the flag, the inputs that usually drive transformer temperature pointed the other way.
Output power and rotor speed ran in different operating regimes over the same period, with output power up 13.6% and rotor speed down 8.2% against the 30 days before. None of these model inputs explained the above-expected winding temperatures. All three phases rose at once while the air around the transformer cooled, which pointed to the cooling rather than to the load.

9 days from flag to fix
SignalKavakenSite team
- Day −24 · 18 Sep 2026 · Signal
Winding temperatures start to drift up
The deviation of the transformer winding temperatures from comparable turbines began rising from an average of 0.3%, following a fluctuating trend.
- Day −8 · 4 Oct 2026 · Signal
Deviation settles at a new level
The deviation from comparable turbines stabilised at 22.7% and stayed there.
- Day 0 · 12 Oct 2026 · Kavaken
Kavaken flags transformer overheating
Phase 1–3 winding temperatures were 30.0% above the expected value and 29.5% above comparable turbines, with a low risk level and an upward trend. Kavaken pointed to the cooling fan or ventilation path. It recommended measuring the fan cut-in sequence, fan current and contactor operation, cleaning the ventilation grilles and air ducts, and verifying the winding temperature protection inputs.
Flag log, Kavaken (translated): Insufficient performance of the transformer cooling fan or ventilation path is the most likely cause of the simultaneous high-temperature divergence across all three phase windings, which has continued despite decreasing ambient temperatures.
- Day 9 · 21 Oct 2026 · Site team · Fix
Faulty fan found, contactor replaced
During checks at the annual maintenance, the site team found the transformer fan faulty. They replaced the faulty fan contactor with a new one.
Flag log, site team (translated): During the checks at the annual maintenance on 21.10.2026, the transformer fan was found to be faulty. The faulty contactor was replaced with a new one.

Figure 2. The faulty transformer fan contactor, replaced by the site team on 21 October 2026. - Day 9 · 21 Oct 2026 · Site team
Flag resolved
The site team closed the flag and recorded the contactor replacement as the action taken.
Flag log, site team (translated): Transformer fan contactor replaced.
Why it stayed hidden
The drift began from a 0.3% deviation and built up over several weeks with a fluctuating trend, so no single day stood out. All three phases rose together, so comparing one phase with another showed nothing unusual. Ambient and nacelle air were cooling at the same time, and the risk was still rated low on the flag date. The problem only showed when the windings were compared with what the conditions predicted and with comparable turbines at the same wind farm.
The outcome
The site team confirmed the cause on site: the transformer fan was faulty, and they replaced the fan contactor on 21 October 2026, Day 9 after the flag. This matches the cause Kavaken pointed to, the transformer cooling fan circuit. The flag was resolved the same day.
The client rated Kavaken's role in the resolution as key.
- Production
- 50 MWh
- Financial
- USD 3,300
- CO2
- 30 t
Avoided-loss potential: Kavaken's estimate of the loss that the early finding prevented. It is not a realized saving.
Takeaway
When all three transformer windings drift up together while ambient air cools, check the cooling fan circuit first, including its contactor. A low-risk flag with a steady deviation can still be a failed fan.