Kavaken flagged a wind turbine gearbox on 1 July 2026. The sump and gear inlet oil temperatures ran 6.9% above expected and 10.8% above similar turbines. It was the second flag in a week. After the first, on 26 June, the site team replaced the thermostatic bypass valve on 28 June, before any SCADA warning. The temperatures did not improve. Kavaken read the bearing data as a cooling problem across the whole oil circuit and pointed to the oil-cooler fans. On 3 July the site team found a stuck contactor in the fan circuit and replaced it. Oil and bearing temperatures improved suddenly, and on 6 August the client wrote that the problem was solved.
Why Kavaken looked past the gears
The gearbox bearing temperatures were rising together with the oil temperatures. But the difference between bearing and oil temperatures was not higher than at similar wind farms, and on most days it was lower. That pattern points away from local friction at a gear or a bearing. It points to the whole oil circuit not shedding enough heat.
Kavaken recommended checking the oil-cooler fans on a windless day: reverse airflow, low flow rate, or the two fan stages failing to engage. It also recommended checking whether the newly replaced thermostatic bypass valve could be stuck.

Two flags, one stuck contactor
SignalKavakenSite team
- Day −2 · 29 Jun 2026 · Signal
First SCADA oil temperature warning
Kavaken had flagged the sump oil temperature on 26 June, about 7.7% above expected. The site team replaced the thermostatic bypass valve on 28 June. One day later, the first SCADA warning on oil temperature came in.
Flag log, Kavaken (translated): After the thermo bypass change on 28 June, the oil temperature warning also came on 29 June.
- Day 0 · 1 Jul 2026 · Kavaken
Kavaken flags the oil temperatures again
GBX OilTemp Sump and GBX OilTemp GearInlt ran 6.9% above expected and 10.8% above the average of similar turbines, with a steady, flat trend. Kavaken pointed to the oil-cooler fans and the new bypass valve.
- Day 1 to 2 · 2 Jul – 3 Jul 2026 · Signal
Stops and high temperature warnings
The turbine stopped twice on low gear inlet oil pressure, for 0.65 and 0.3 hours. A high sump oil temperature warning lasted 13.97 hours, and a high gear inlet oil temperature warning followed for 6.42 hours.
- Day 2 · 3 Jul 2026 · Site team · Fix
Stuck fan contactor found and replaced
The site team inspected the oil-cooler fan circuit, found a stuck contactor and replaced it.
Flag log, site team (translated): Contactor sticking was detected on 03/07/2026. The part was replaced. Monitoring should follow.

Figure 2. The stuck fan contactor shows arc and soot marks on its pole windows. The contactor of the same type next to it has clean windows. - Day 35 · 5 Aug 2026 · Kavaken
Kavaken confirms a sudden improvement
After a month of monitoring, Kavaken confirmed that the sump and inlet oil temperatures and the gearbox high-speed shaft bearing temperature had improved suddenly after the 3 July intervention.
Flag log, Kavaken (translated): The intervention on 3 July was successful. It caused a sudden improvement in the sump and inlet oil temperatures and the gearbox HSS bearing temperature that this flag is about.
- Day 36 · 6 Aug 2026 · Site team
Client reports the problem solved
The client confirmed the result and the case was resolved.
Flag log, site team (translated): The problem has been solved.
- 17 Oct 2026 · Site team
Photo confirms which contactor stuck
From a site photo, Kavaken identified the stuck contactor by the arc and soot marks on its pole windows, which a neighbouring contactor of the same type did not have. The client confirmed the identification.
Why it stayed hidden
The first action came before SCADA raised anything: the site team replaced the thermostatic bypass valve on 28 June on Kavaken's first flag, and the first oil temperature warning only came on 29 June. With the usual fix already done, the issue looked handled. The bearing-to-oil temperature gap gave no sign of a worn gear or bearing. The cause sat outside the gearbox, in the electrical circuit of the cooler fans.
The outcome
Kavaken confirmed the result in the data: after the contactor replacement on 3 July, the sump and inlet oil temperatures and the gearbox high-speed shaft bearing temperature improved suddenly. On 6 August the client wrote that the problem was solved.
A site photo later showed arc and soot marks on the pole windows of the replaced contactor, and clean windows on the same type of contactor next to it. The client confirmed that this was the contactor that had stuck.
The client rated Kavaken's role in the resolution as key.
- Production
- 530 MWh
- Financial
- USD 27,600
- CO2
- 330 t
Avoided-loss potential: Kavaken's estimate of the loss that the early finding prevented. It is not a realized saving.
Takeaway
When a new bypass valve does not bring gearbox oil temperatures down and the bearing-to-oil gap looks normal, check the cooler fan circuit, contactors included, before the gearbox itself.