Kavaken flagged a high-risk overheating pattern in a wind turbine's generator windings. All six generator segment temperatures and their average had stepped up and stayed high: 33.0% above the expected value and 40.5% above similar turbines at the farm. Output power was stable, and nacelle and ambient temperatures were falling. Nothing in the operating conditions explained the heat, and no SCADA warning was raised. Kavaken pointed to inadequate generator cooling or heat transfer as the most likely hypothesis. Eleven days after the flag, the OEM replaced the generator fan motor. The deviation then disappeared, and similar turbines stayed normal.

Hotter generator, cooler surroundings
Over the 14 days before the flag, compared with the preceding 30 days, the generator and its surroundings moved in opposite directions.
Operational or environmental heating could not explain the rise. After the step, the generator cooler inlet temperature fell 21.2% and the outlet temperature fell 29.6%. Kavaken noted that a flow measurement was needed to assess this change in terms of heat transfer.
36 days, step by step
SignalKavakenOEMSite team
- Day −6 · 21 Sep 2026 · Signal
Segment temperatures step up and stay
The average deviation from the expected value across all generator segment sensors jumped from 1.9% to 37.5%. The deviation from similar turbines jumped from 6.3% to 44.3%. The new levels were sustained.
- Day 0 · 27 Sep 2026 · Kavaken
Kavaken flags generator winding overheating
Kavaken raised a high-risk flag on generator segment temperatures 1–6 and their average. The most likely hypothesis was inadequate generator cooling or heat transfer. Kavaken recommended reviewing the alarm logs, measuring liquid circuit flow and cooler heat transfer, checking temperatures with independent measurements and assessing operation against the manufacturer's limits.

Figure 2. On the flag date the turbine's generator segment temperatures averaged 99.3 °C, against 58.7 °C for similar turbines at the farm: 40.5% higher and the highest reading. - Day 11 · 8 Oct 2026 · OEM · Fix
OEM replaces the generator fan motor
The OEM team replaced the generator fan motor on the turbine.
Flag log, site team (translated): On 08.10.2026 the generator fan motor on the turbine was replaced by the OEM.
- Day 36 · 2 Nov 2026 · Kavaken
Kavaken confirms the deviation has gone
The deviation had stayed at the level of the flag until 8 October and then disappeared abruptly. It had not been seen for 24 days, and similar turbines were normal. Kavaken asked the site team for the intervention details.
Flag log, Kavaken (translated): The deviation stayed at the level at which the flag was opened until 08.10.2026, then disappeared abruptly after that date and has not been seen for 24 days. The deviation is also normal on similar turbines.
- Day 36 · 2 Nov 2026 · Site team
Site team confirms the fault was cleared
The site team confirmed that the fault was cleared by the OEM team on 8 October, and the flag was resolved.
Flag log, site team (translated): On 08.10.2026 the fault was cleared by the OEM team.
Why it stayed hidden
The turbine kept producing normally, with stable output power, and no SCADA warning was raised. The weather was getting cooler, and the generator cooler inlet and outlet temperatures fell after the step. A check of the cooling circuit temperatures alone would not have pointed to a problem. The issue became visible only when the segment temperatures were compared with their expected values under the same conditions and with similar turbines at the farm.
The outcome
The fix was confirmed in the monitored data. The deviation disappeared after the generator fan motor was replaced on 8 October. It had not returned 24 days later, and similar turbines stayed normal. The Kavaken chart shows the average segment temperature back in the expected band, with a peak of 75 °C since the repair.
The client rated Kavaken's role in the resolution as key.
- Production
- 360 MWh
- Financial
- USD 23,900
- CO2
- 230 t
Avoided-loss potential: Kavaken's estimate of the loss that the early finding prevented. It is not a realized saving.
Takeaway
A step change in winding temperatures while output is stable and the weather is cooling points to the cooling path, not the load. Compare segment temperatures with similar turbines, and check the generator fan and cooling flow before the winding insulation pays for it.